Premium

The eight procurement considerations when buying a sodium-ion BESS 

LinkedIn
Twitter
Reddit
Facebook
Email

Sodium-ion looks set to finally arrive in the grid-scale BESS industry, but what should the prospective first-movers on the technology be thinking about when considering buying products?  

Arthur Claire, director of technology at technical compliance and quality engineering consultancy Sinovoltaics discussed the topic in a recent webinar put on by the firm. It follows a real inflection point for sodium-ion (Na-ion) battery technology in the past 12 months, see all our coverage of the technology here.

Put cell chemistry in the contract 

The first consideration is to put the chemistry of the cell in the BESS procurement contract, he said in the ”Sodium-ion BESS Ready for Prime Time? A Technical and Commercial Reality Check’ webinar.  

There are three main cathode families that can be used to construct the cells inside a BESS, he explained: layered oxides, polyanion (NFPP), and Prussian blue analogues.  

This article requires Premium SubscriptionBasic (FREE) Subscription

Try Premium for just $1

  • Full premium access for the first month at only $1
  • Converts to an annual rate after 30 days unless cancelled
  • Cancel anytime during the trial period

Premium Benefits

  • Expert industry analysis and interviews
  • Digital access to PV Tech Power journal
  • Exclusive event discounts

Or get the full Premium subscription right away

Or continue reading this article for free

The cathode chemistry should be stated on any BESS procurement contract. It can be a part of the data sheet specifications, but the cell model and manufacturer should be clearly visible because you want it to be clear what it is that you’re actually buying and what you need to include as part of the procurement contract.  

This is more important than Li-ion as Na-ion is a much newer technology, so seeing more data sheets and technical documents to ensure that the exact technology is going to meet the needs of the installation is critical and is the first major step in any new Na-ion BESS installation. This should be done with Li-ion as well, but with Na-ion specifications being more unfamiliar due to the ubiquitous presence of Li-ion in the market today, it is more important to be thorough. Marketing documents and final technical datasheets can sometimes be different, which may not be as apparent or noticeable with unfamiliar battery chemistries, but putting the cell chemistry into the contract can help to resolve any potential issues a lot easier down the line if there is a discrepancy―as marketing data is not necessarily guaranteed and cannot be used in claim management. 

EMS and PCS integration for different voltage to LFP 

The second consideration for any new Na-ion BESS installation is energy management system (EMS) and power conversion system (PCS) integration. The voltage discharge curve has a lot more slope than LFP (which has become the standard BESS chemistry). The voltage discharge curve in LFP is flat between 20–80% state of charge (SOC), with a typical voltage of 3.2V, whereas Na-ion falls from 3.3V to 1.5V. Because there is a more defined discharge slope, the SOC is easier to calculate than LFP, which tends to have a 5% SOC uncertainty because of the flat voltage curve. 

However, a Na-ion doesn’t behave like an LFP cell, which needs to be accounted for when choosing the cells. The low end of the voltage is a lot lower than LFP. On the DC side, LFP will tend to stay around 1400V, but Na-ion can swing between 600-1400V. So, when choosing Na-ion cells for the BESS, it’s also important to choose a PCS that can handle those low voltages. Additionally, at constant power, the current needed to discharge at low SOCs is going to be much higher than in LFP cells, so the PCS needs to be able to handle these discharge dynamics as well. On the EMS side, most EMS are being designed for LFP in terms of the discharge energy and SOC windows, so you need to ensure that any EMS (and its rules) integrated into the BESS will also apply to Na-ion batteries. 

To make sure that this is not an issue, Claire stated that a full integration test between the EMS, PCS and the BESS container should be performed before the first delivery to make sure that you don’t start to find bugs when everything is already on site. Claire also recommended that anyone buying Na-ion BESS should also liaise with the PCS supplier to make sure that they are aware that it’s a sodium-ion DC block and that they need to make it work without any issues. 

Lack of field data means it’s hard to quantify true calendar life 

The other consideration to be aware of is that there is not much field data, on a utility scale level, for Na-ion cells compared to LFP. This is because LFP has around 10 years of data coming from the field whereas Na-ion is relatively new―with the oldest field test site being from only 2024. There are a lot of claims of 10,000–20,000 cycles at one cycle a day, which would equate to a calendar life of 27-55 years. However, it’s very difficult to estimate whether a Na-ion cell would last this long and there is a lack of utility data to prove it (and will take a long time to do so). It’s also usually the cases that the various environmental and operational factors affect the life compared to what is seen in the test data. 

It’s something that has been seen with LFP, where only the first 1,000–2,000 cycles have been tested. Beyond this, the cycle life uses projected/modelled values for up to 10,000 cycles, or 20,000 cycles in the case of Na-ion. So, to try and get an idea of the true aging of the Na-ion cell you’re procuring, Claire stated that you should ask for the raw aging data from your manufacturer for different cases, different temperature, different cycles, different C-rates, different depth of the charge. This will allow you to build a more realistic picture of your battery performance. If you have the budget, Claire also recommended spending some money on an independent battery cell lab test to anticipate the early degradation of the cell and to try to stress those new Na-ion cells with overvoltage or different thermal conditions. 

Check for warranty exclusions 

Linked to the projected cycle life, degradation warranties of 10,000 or 20,000 cycles rely on simulations, modelling, and predictions rather than historical field data. So, understanding what the warranty includes and what is excluded is critical. Anyone purchasing the BESS needs to look at the exclusions in the temperature, cycles per day, C-rates, and SOC windows, and what happens to those warranties if you operate outside those warranty conditions. It could be that the warranty is downgraded, but it could also mean that the warranty becomes void, so these operational constraints need to be checked before purchasing. According to Claire, the average warranty is 20 years to 70% state of health (SOH) at one cycle per day, 0.25P, but it can vary. 

So, there needs to be a clear visibility of the warranty risks, and Claire stated that you should list every exclusion and every condition that will void the warranty and what are the risks that you actually cross those. The warranty exclusion list should also be checked against the use case, because the warranty for -30°C is not relevant if it is being sited in the Middle East, for example. 

The gap in standard certifications to be aware of 

There are two main standards for BESS: UL for North America and IEC for the rest of the world. The key standard for BESS is IEC 62619, which is meant for Li-ion cells. The Na-ion equivalent is IEC 63635, but that is still in draft, so some suppliers are showing IEC 62619 for Na-ion BESS as well as Li-ion BESS. So, there is a certification gap from an IEC standpoint currently. It’s expected that the new IEC 63635 will be released at the end of this year or sometime next year. 

However, for the UL standards in North America, UL 1973 has included Na-ion cells since 2022 and UL 9540A has include Na-ion testing methods since 2025. So, there is also a geographical certification gap. Claire stated in his talk that purchasers should ask for all the certificates and the full test report to see what tests have actually been performed on the Na-ion cells―as well as what is considered as a pass or potentially pass with limitations. With Na-ion standards changingly rapidly as the technology becomes more mature, procurement contracts need to be checked that the standards being reported are the latest standard and are related to the cell and BESS that is part of the procurement contract for the BESS being bought, and that the certificates are also tied to the factory that the BESS is being bought from. 

New factories and less experience can be a potential issue 

Another consideration is that new factories can have less experience with the whole process. Claire stated that they have previously visited new factories, and during a Na-ion factory acceptance test (FAT) at one unnamed factory, there was no PCS and no ability to perform capacity or performance test―which is a major issue. Part of the FAT checklist was also negotiated as part of the test protocol, which is not professional practice. Claire also stated that certificates were requested repeatedly but not provided and industry professionalism was lacking. It was also found that the factory was using an OEM and likened it to ‘buying a Porsche BESS only to realise that it’s manufactured at a Dacia factory’. So, these are things that any buyers should be aware of and lookout for when choosing a factory, and Claire stated that since Na-ion is a new technology, buyers should make third-party FAT supervision part of the contractual milestone with clear pass/fail criteria, and if the FAT is a fail, then there is no shipment. 

Scaling production lines will bring teething issues 

There is also the matter of scale. The big battery manufacturers are just starting GWh-scale deliveries this year, and it’s expected to grow significantly in the coming years. With Na-ion manufacturing lines being new, anyone purchasing a Na-ion BESS will need to be aware that there are going to be teething issues―much like there is when you’re scaling up any new technology. For example, there could be issues with the yield of the process and the components being used, as the process setting and bill of materials will keep moving. Production issues will slow down over time, and as more GWh of BESS are shipped, but it’s a process that any potential buyers need to be aware of. As things move fast, it’s also possible that certifications may come from a pilot line and not a scaled-up production line, so prospective buyers need to be vigilant of this, just in case. Claire recommended tying the certificates to the factory address, making sure that the plant that is building your BESS is actually the one written on the certificate and audit it, and to audit the bill of materials as part of the procurement contract. 

Evaluating financial state of supplier 

With Na-ion being a fast-moving industry, choosing a supplier whose product is going to survive is important. LFP is already cheap and getting cheaper, so Na-ion will need to compete with it on price. So, it’s likely that many Na-ion factories are going to go bust while trying to scale and lower both production and overall cell costs to compete with LFP. It’s already been an issue in the early stages of the industry, and more factories are likely to become bankrupt.  

So, choosing the right BESS supplier will be critical, because if the company goes bankrupt, there will be no more performance warranties, no more spare parts, and potentially no further support. There’s the potential, with the industry being fast moving, that some products will be discontinued in just a few years as well, as more advanced products are sold to market. So, buyers will need to plan for where they can get spare parts from in case this happens. Claire stated that any prospective buyers should evaluate the bankability of their supplier before purchasing. 

Read Next